AC help
EDIT: Solved. Thank you
Hello, long story short last year my AC worked fine. With the help of a friend we installed a new smart thermostat this winter, he also changed some control wiring in the furnace that he said was wrong. The furnace and thermostat worked fine the rest of winter. Come time to turn on the AC it doesn’t work.
I have 240v going In. I have 0V between the control wires, but I have 27v from either control to ground. (Wether or not it’s calling for AC at the stat)
If I press the plunger of the contactor it turns on and blows cold.
We tried a new contactor but same thing.
Should I have 24v between control lines…?
What else? Thanks in advance