▲ 38 r/HVAC

Customer called for ac not cooling.

Indoor temp was 75 degrees

Outside is 80 degrees

7 year old trane xr 410a

10 degree delta t

Filter clean

Condenser clean.

This looked to me like liquid line restriction.

We changed txv and drier but pressure are the same.

Apparently this compressor was changed out by a 1 man in a van type of company 1 week prior to us coming out.

We confirmed that the compressor they installed is the correct one

Not really sure what's going on here but we are thinking possibly it's an oil logged evaporator

u/Best_Ad_2263 — 18 days ago