Working on an older rack system (R404A) with a Sporlan SORIT-15 EPR with integral solenoid stop/pilot.

Trying to narrow down whether this is a pilot issue or if the main valve body is actually failing.

Observed behavior:

  • Case normally runs ~40–50 psi at the header
  • Upstream of the EPR sits around ~75 psi when pilot is open
  • Manually closing the pilot feed drops suction to ~50 psi (valve goes wide open as expected)

Issues:

  • EPR adjustment has little to no effect on suction pressure
  • During defrost, I’m reading 0V across the solenoid coil (208/240V), but the case still appears to be feeding / not pumping down properly
  • Defrost is ineffective unless manually intervened

What I’ve verified:

  • Defrost timer is switching correctly
  • Coil is de-energized in defrost
  • System responds when pilot pressure is manually manipulated

Trying to confirm direction before replacing parts — there’s a significant difference between replacing the pilot assembly vs the entire valve body.

Questions:

  1. Do these symptoms typically point to a failing pilot assembly (KY1005)?
  2. Have you seen similar behavior with a good main valve but bad pilot section?
  3. Anything else you’d check before committing to a pilot replacement?

Appreciate any input from anyone who’s worked on these older Sporlan EPR setups.